Sontheimer, Henrik ; Kind, Johannes ; Stephan, Peter ; Gambaryan-Roisman, Tatiana (2024)
Numerical simulation of drop array impingement onto a superheated wall.
ICLASS 2024, 16th Triennial International Conference on Liquid Atomization and Spray Systems. Shanghai, China (23.06.2024-27.06.2024)
doi: 10.26083/tuprints-00027601
Conference or Workshop Item, Secondary publication, Publisher's Version
Text
paper_published.pdf Copyright Information: CC BY 4.0 International - Creative Commons, Attribution. Download (1MB) |
Item Type: | Conference or Workshop Item |
---|---|
Type of entry: | Secondary publication |
Title: | Numerical simulation of drop array impingement onto a superheated wall |
Language: | English |
Date: | 5 July 2024 |
Place of Publication: | Darmstadt |
Year of primary publication: | 2024 |
Place of primary publication: | Shanghai |
Collation: | 10 ungezählte Seiten |
Event Title: | ICLASS 2024, 16th Triennial International Conference on Liquid Atomization and Spray Systems |
Event Location: | Shanghai, China |
Event Dates: | 23.06.2024-27.06.2024 |
DOI: | 10.26083/tuprints-00027601 |
Corresponding Links: | |
Origin: | Secondary publication |
Abstract: | Spray cooling is a very efficient method for thermal management of high-performance electronics. The performance of spray cooling is determined by the fluid dynamics and the heat transport when a single drop or multiple drops hit the superheated wall. To understand this process, we numerically study the generic situation of simultaneous impingement of periodic drop arrays onto a superheated wall. We study three different cases in which the distance between the drops varies. The refrigerant used is perfluorohexane (FC-72) in a pure vapor atmosphere under saturation conditions. Drops impinge at moderate Reynolds and Weber numbers, where no splashing occurs during single drop impingement. The wall temperature is above the saturation temperature of the fluid but below the onset of nucleate boiling. Simulations are performed using the OpenFOAM software library, taking into account a dynamic contact angle, evaporation and conjugate heat transfer. We show that the coalescence of more than two drops results in the formation of a liquid jet. A small distance between the drops results in the formation of a thin liquid film while a large distance results in small drops sitting on the wall. In the latter case, the largest amount of heat is transferred, but the occurrence of dry spots is undesirable for cooling applications. The results contribute to a better understanding of spray cooling and provide a perspective for efficient spray cooling. |
Status: | Publisher's Version |
URN: | urn:nbn:de:tuda-tuprints-276016 |
Classification DDC: | 600 Technology, medicine, applied sciences > 620 Engineering and machine engineering |
Divisions: | 16 Department of Mechanical Engineering > Institute for Technical Thermodynamics (TTD) DFG-Collaborative Research Centres (incl. Transregio) > Collaborative Research Centres > CRC 1194: Interaction between Transport and Wetting Processes > Research Area C: New and Improved Applications > C02: Multiscale Investigations of Boiling of Complex Fluids on Complex Surfaces DFG-Collaborative Research Centres (incl. Transregio) > Transregios > TRR 75 Droplet Dynamics Under Extreme Ambient Conditions |
TU-Projects: | Bund/BMWi|03EN2026A|LoTuS DFG|TRR75|TP C1 TRR 75 DFG|SFB1194|TP C02 Stephan |
Date Deposited: | 05 Jul 2024 12:07 |
Last Modified: | 08 Nov 2024 11:13 |
URI: | https://tuprints.ulb.tu-darmstadt.de/id/eprint/27601 |
PPN: | 519626702 |
Export: |
View Item |